Surge Protection
KEN-300/G Surge Protector

Requirement class to VDE 0675: B or B+C
Requirement class to EN 61643-11: Type 1 or 1+2
Requirement class to IEC61643-1: Class I or Class I+II
Location of use: Branch sub-distribution boards
Protection modes: L/N-PE,L-PE,L-N
Protective element: High Energy GDT or GDT + MOV
Surge discharge ratings: Iimp=25kA
Housing: Modular design

How to name our products

KEN-300/G+/1P - 320
KEN: Model
300: Type
G or G+ : Protective element: GDT or GDT +MOV
1P: Combination: 1P
320: Uc: 320VAC.

KEN-300/G/1P-320

Surge Protector Max. continuous operating voltage(AC/DC)Uc:320 rms
Nominal discharge current(8/20) In:100kA      Max. discharge current(8/20) Imax:200kA
Impulse discharge current(10/350) Iimp:25kA
Measured limiting voltage at 1.2/50 6kV waveform: ≤1.5kV
Residual voltage at 25kA(8/20) Ures:<1.5kV
Follow current at 50/60 Hz: 3kA rms (UC:320V) / 5kA rms (UC:255V)     
Protective element: GDT

Surge Protector for power Solutions

KEN-300/G/1P-320

Surge Protector Max. continuous operating voltage(AC/DC)Uc:320 rms
Nominal discharge current(8/20) In:25kA      Max. discharge current(8/20) Imax:200kA
Impulse discharge current(10/350) Iimp:25kA
Measured limiting voltage at 1.2/50 6kV waveform: ≤1.5kV
Residual voltage at 25kA(8/20) Ures:<1.5kV
Follow current at 50/60 Hz: 3kA rms (UC:320V) / 5kA rms (UC:255V)     
Protective element: GDT+MOV

Surge Protector for power Solutions